Testwork carried out in the cooling water circuit at the Yabulu treatment plant of the Greenvale Joint Venturers (Metals Exploration Queensland Pty. Ltd. and Freeport Queensland Nickel Incorporated) since 1980 has resulted in significant improvements to both fouling and corrosion control. At the same time corrosion inhibitor costs have been reduced._x000D_
Acrylate-type silt dispersants were identified as the most effective means of sediment control in the circuit. An increase in the cathodic component of the corrosion inhibitor coupled with a relatively minor adjustment to water pH has yielded a two to three fold reduction in corrosion rate. It has been established that these lower corrosion rates can be sustained in the face of a 20% reduction in corrosion inhibitor addition rate. Further improvements are indicated with a change of raw water algicide.